Technical specification for transformers TMG

Home Three-phase oil-immersed transformers Transformers TMG Technical specification for transformers TMG

Technical specification for transformers TMG 

 Transformer type
Winding connection
schemes and groups
 Short-circuit loss, Watt
 Impedance voltage, %
Standby loss, Watt 

 TMG-25/10(6)/0,4

Y/Yn-0;  Y/Zn-11

600 

4,5 

115 

 TMG-40/10(6)/0,4

Y/Yn-0;  Y/Zn-11 

900

150

 TMG-63/10(6)/0,4

Y/Yn-0;  D/Yn-11; Y/Zn-11

1270

210

 TMG-100/10(6)/0,4

Y/Yn-0;  D/Yn-11; Y/Zn-11

1970

270

 TMG-160/10(6)/0,4

Y/Yn-0;  D/Yn-11; Y/Zn-11

2700

400

 TMG-250/10(6)/0,4

Y/Yn-0;  D/Yn-11

3700

540

Y/Zn-11

3900

 540

 TMG-400/10(6)/0,4

Y/Yn-0;  D/Yn-11

5400

770

Y/Zn-11

5600

770

 TMG-630/10(6)/0,4

Y/Yn-0; D/Yn-11

7600

5,5

1050

TMG-1000/10(6)/0,4

 Y/Yn-0;  D/Yn-11

10500

1550

TMG-1250/10(6)/0,4

 Y/Yn-0;  D/Yn-11

13500

6,0

1650

 

 

 

 

+7 (3852) 46-67-14
Contact us

Articles

Product catalogue

Three-phase oil-immersed hermetically-sealed distribution transformers (TMG)

Three-phase oil-immersed hermetically-sealed energy-efficient distribution transformers (TMGe2)

Three-phase oil-immersed hermetically-sealed flanged distribution transformers (TMGF)

Three-phase oil-immersed distribution transformers (TM)

Three-phase oil-immersed hermetically-sealed pole-mounted distribulion transformers (pole-mounted TMG)

One-phase oil-immersed hermeticallly-sealed distbution transformers (pole-mounted OMG)

Three-phase oil-immersed hermetically-sealed transformers for electrosubmersible pump supply (TMGPN)

Indoor package transformer substations

Pole-mounted package transformer substations on one concrete column SV-110 (SV-105)

Pole-mounted package transformer substations on four consoles PT-43